Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

association only with specified values for TSelector, PSelector, and SSelector #413

Open
wants to merge 1 commit into
base: v1.5
Choose a base branch
from

Conversation

A-bazhdar
Copy link

@A-bazhdar A-bazhdar commented Oct 26, 2022

Hi
I added lines to ensure that clients can create associations only with the specified values for TSelector, PSelector, and SSelector.

According to the UCA Document "Conformance Test Procedures for Server Devices with IEC 61850-8-1 interface",
mentioned parameters should be as defined within the ICD file. Otherwise, the server device should fail the association and send the response- to the client.

also, see:

  • Siemens PIXIT files for Multi-Functional Protective Relays(for example this Link section 2.1)
  • Easergy PIXIT files for (This Link section 2.1)

… the specified values for TSelector, PSelector and SSelector