You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
Users doing detailed engineering checks reported problems with Standard 62.1 Ventilation Rate Procedure results. Found mistakes in code, one copy paste error for term Fb and a term missing in an equation for calculating zone Evz.
Fb should equal Ep
We see Fb values for cooling design match Ep values for heating design. Code inspection shows FbByZoneCool variable used where it should be FbByZoneHeat
User reports Evz values are coming out too high and sometimes even negative, code inspection finds missing the Ep term in missing in the equations for zone Evz.
To low Evz can cause systems to oversize when using VRP.
Details
Some additional details for this issue (if relevant):
Platform (Windows, current develop)
Version of EnergyPlus (if using an intermediate build, include SHA)
Unmethours link or helpdesk ticket number
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
Issue overview
Users doing detailed engineering checks reported problems with Standard 62.1 Ventilation Rate Procedure results. Found mistakes in code, one copy paste error for term Fb and a term missing in an equation for calculating zone Evz.
Fb should equal Ep
We see Fb values for cooling design match Ep values for heating design. Code inspection shows FbByZoneCool variable used where it should be FbByZoneHeat
User reports Evz values are coming out too high and sometimes even negative, code inspection finds missing the Ep term in missing in the equations for zone Evz.
To low Evz can cause systems to oversize when using VRP.