In the attached IDF files, I have a simple DOAS air loop with 3 components (Supply Fan, DX Cooling Coil, Dehumidification Reheat Coil). The DOAS has a cooling temperature setpoint of 26.7 C and a Maximum Humidity Ratio setpoint of 0.0089 kg water/kg dry air.
In the "CoilSystem:Cooling:DX" object that wraps the DX cooling coil, I set the "Run on Latent Load" to Yes, which means the coil should run if there is a latent load, even if there is no sensible load.
When the DX Cooling Coil is a "Coil:Cooling:DX:SingleSpeed" object, the DX coil runs ok to maintain the cooling coil outlet maximum humidity ratio setpoint.
However, when the DX cooling coil is a "Coil:Cooling:DX:VariableSpeed" object, the DX cooling coil will only run when there is a sensible load. The coil remains off for the time period with only latent load but no sensible load.
Based on this results, I think there is either a bug in the "CoilSystem:Cooling:DX" object or the "Coil:Cooling:DX:VariableSpeed" object.
Details
Some additional details for this issue (if relevant):
Issue overview
In the attached IDF files, I have a simple DOAS air loop with 3 components (Supply Fan, DX Cooling Coil, Dehumidification Reheat Coil). The DOAS has a cooling temperature setpoint of 26.7 C and a Maximum Humidity Ratio setpoint of 0.0089 kg water/kg dry air.
In the "CoilSystem:Cooling:DX" object that wraps the DX cooling coil, I set the "Run on Latent Load" to Yes, which means the coil should run if there is a latent load, even if there is no sensible load.
When the DX Cooling Coil is a "Coil:Cooling:DX:SingleSpeed" object, the DX coil runs ok to maintain the cooling coil outlet maximum humidity ratio setpoint.
However, when the DX cooling coil is a "Coil:Cooling:DX:VariableSpeed" object, the DX cooling coil will only run when there is a sensible load. The coil remains off for the time period with only latent load but no sensible load.
Based on this results, I think there is either a bug in the "CoilSystem:Cooling:DX" object or the "Coil:Cooling:DX:VariableSpeed" object.
Details
Some additional details for this issue (if relevant):
Platform (WIndows 11, 64bit)
Version of EnergyPlus (24.2)
Unmethours link or helpdesk ticket number
Defect files
DOAS_SingleSpdCoil.idf.zip
DOAS_VariableSpdCoil.idf.zip